VOKERA Linea Manual de servicio Pagina 17

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 44
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 16
15
5.1 GAS SUPPLY INSTALLATION
Inspect the entire installation including the gas meter, test for
tightness and purge. Refer to BS 6891 for specific instruction
.
5.2 THE HEATING SYSTEM
The appliance contains components that may become damaged or
rendered inoperable by oils and/or debris that are residual from the
installation of the system, consequently it is essential that the system
be flushed in accordance with the following instructions.
5.3 INITIAL FILLING OF THE SYSTEM
Ensure both flow and return service valves are open, remove
appliance casing as described in 4.7.1, identify the automatic air
release valves (AAV) and loosen the dust cap/s by turning the cap
anti-clockwise one full turn.
IMPORTANT, THERE ARE NO MANUAL AIR RELEASE VALVES
LOCATED ON THE APPLIANCE. Ensure all manual air release
valves located on the heating system are closed.
Connect the filling loop as shown in fig. 3, slowly proceed to fill the
system by firstly opening the inlet valve connected to the flow valve,
and then turning the lever on the combined stopcock and check
valve, to the filling position (see fig. 18). As water enters the system
the pressure gauge will begin to rise. Once the gauge has reached
1 BAR close both valves and begin venting all manual air release
valves, starting at the lowest first. It may be necessary to go back and
top-up the pressure until the entire system has been filled. Inspect
the system for water tightness, rectifying any leaks.
5.4 INITIAL FLUSHING OF THE SYSTEM
The whole of the heating system must be flushed both cold and hot
as detailed in 5.8. Open all radiator or heating valves and the
appliance flow & return service valve. Drain the boiler and system
from the lowest points. Open the drain valve full bore to remove any
installation debris from the boiler prior to lighting. Refill the boiler
and heating system as described in 5.3.
5.5 FILLING THE HOT WATER SYSTEM
Close all hot water outlets, turn appliance stopcock to the normal
operating position (fig. 18), slowly open each outlet until air has
been expelled and clear water is discharged.
Check pipe-work etc. for water tightness.
5.6 PRE-OPERATION CHECKS
Before attempting the initial lighting of the appliance, the following
checks must be carried out:
- ensure all gas service valves from the meter to the appliance are
open and the supply pipe has been properly purged;
- ensure the proper electrical checks have been carried out, (see
7.8) particularly continuity, polarity, and resistance to earth;
- ensure the 3 AMP fuse – supplied with the appliance – has been
fitted;
- ensure the system has been filled, vented, and the pressure set
to 1 BAR;
- ensure the flue system has been fitted properly and in accordance
with the instructions;
- ensure all appliance service valves are open.
5.7 INITIAL LIGHTING
Ensure the electrical supply to the appliance is switched on. Press
the ON/OFF switch to switch the appliance ON (indicated by active
display), ensure any external controls are switched to an ‘ON’
position and are calling for heat.
After being powered, the boiler begins an automatic vent cycle
lasting approximately 2 minutes. The display indicates “sf” and the
“function selection indicators” light up in sequence. Press the
MODE button to interrupt the automatic vent cycle.
Press the heating button, the appliance will now operate in the
Winter
mode as described in 1.2. Should the appliance fail to ignite,
refer to 5.6 and/or section 7 (mode of operation, parameter setting,
& faultfinding).
5.7.1 CHECKING GAS PRESSURE AND COMBUSTION
ANALYSIS
The appliance is factory set and requires no additional adjustment
once installed.However to satisfy the requirements of GSIUR 26/9
(I.S. 813 ROI), it will be necessary togas rate the appliance using
the gas meter that serves the appliance.If the installation does not
include a gas meter (for example LPG) and there are nomeans by
which to calculate the gas rate, then a combustion analysis test
must becarried out in accordance with BS 7967 (UK) to ensure the
appliance is left workingsafely and correctly.Additionally, if the gas
valve has been adjusted, replaced, or the appliance has
beenconverted for use with another gas type, then it becomes
necessary to carry out acombustion analysis/check to ensure that
correct combustion is occurring.If there are no means to gas rate
the appliance and/or carry out a combustion analysischeck, then it
will not be possible to complete the commissioning procedure.
Details on how to carry out the combustion analysis can be found
in section 7.
IMPORTANT
It’s imperative that a sufficient dynamic – gas – pressure is
maintained at all times.Should the dynamic gas pressure fall below
an acceptable level, the appliance maymalfunction or sustain
damage
5.8 FINAL FLUSHING OF THE HEATING SYSTEM
The system shall be flushed in accordance with BS 7593. Should
a cleanser be used, it must be suitable for Copper and Aluminium
heat exchangers. It shall be from a reputable manufacturer and
shall be administered in strict accordance with the manufacturers’
instructions and the DWTA code of practice.
NOTE
Chemicals used to cleanse the system and/or inhibit corrosion
must be pH neutral, i.e. they should ensure that the level of the pH
in the system water remains neutral.
Premature failure of certain components can occur if the level of
pH in the system water is out-with normal levels.
5.8.1 INHIBITORS
See Section 3 “General Requirements”.
5.9 SETTING THE BOILER OPERATING TEMPERATURE
The flow outlet temperature can be adjusted between 39 °C - 80 °C
via the “Heating temperature adjustment button” (see fig.2).
5.9.1 SETTING THE DOMESTIC HOT WATER TEMPERATURE
The DHW outlet temperature can be adjusted between 35 °C - 60
°C via the “DHW temperature adjustment button” (see fig. 2).
5.9.2 INFORMATION MODE
By pressing the
key, the InFO word appears on display. By turning
the selector A, the display shows, one by one, the information
described below.
Info list (fig. 19)
Info 1 displays the external temperature recorded by the probe,
only if an external probe is connected
Info 2 displays the system pressure, accompanied by the filling
symbol
normal operating
position
filling position
closed
position
Fig. 18
SECTION 5 - COMMISSIONING
Vista de pagina 16
1 2 ... 12 13 14 15 16 17 18 19 20 21 22 ... 43 44

Comentarios a estos manuales

Sin comentarios